Recloser | Eaton's Cooper Power Systems



- Application: Overcurrent protection on the medium voltage power grid
- 27kV, 16kA & 38kV, 12.5kA
- Solid insulation, Vaccum Interrupter.
- Integrated 6 voltage sensors on both sides for loop connection
- IEC 62271_111/ IEEE C37.60 (2012)
- Type test: Powertech lab (STL member)

- Comply with SCADA/DAS connection

Table 1: Rated voltage (kV)

Description 15 kV 27 kV 38 kV

  Maximum voltage

  Impulse withstand voltage (BIL)

  Power frequency withstand voltage - Dry

  Power frequency withstand voltage - wet

15,5 kV

110,0 kV

50 kV

45 kV

27,0 kV

125,0 kV*

60 kV

50 kV

38,0 kV

170,0 kV

70 kV

60 kV

* Optional 150kV.

Table 2: Rated current (kV)

Description 15 kV 27 kV 38 kV

 Rated continuous current

 Short circuit breaking current

 Symmetrical short-circuit current

 Peak short-circuit breaking current

630 A*

12,5 kArms**

12,5 kArms**

31,5 kApeak**

630 A*

12,5 kArms**

12,5 kArms**

31,5 kApeak**

630 A*

12,5 kArms**

12,5 kArms**

31,5 kApeak**

            * 800 A option.

            ** 16.0 kArms option (40 kApeak Peak short-circuit breaking current)

Salient features:

  •          The NOVAi recloser is a 3-phase, vacuum cut-out chamber, which is a successful combination of four advanced technologies: cycloaliphatic-epoxy solid-insulated encapsulation, high-performance vacuum cut-out chamber, low-energy operating mechanism reliable and an Eaton's Cooper Power Systems automatic microprocessor controller. Polymer solid insulators are highly resistant to ozone, moisture, pollution, UV, and trace.